Operating and installation manual for VR 61 mixer module10
5 Assembly
The mixer module VR 61 is wall-mounted in proximity
with the associated function units .
The adjustment of all required parameters is carried out
using the controller VRC 430 or VRC 430f via eBUS. All
connections of the associated function units take place
directly on the mixer module VR 16 via ProE terminals.
5.1 Scope of delivery
Before starting the installation, check the scope of
delivery for completeness and lack of damage.
Pos. Number Component
1 1 Mixer module VR 61
2 1 VR 10 standard sensor
3 1 Mounting accessories (screws, plugs)
Table 5.1 Scope of delivery of the mixer module VR 61
h
Note!
Depending upon the configuration of the heating
system, additional sensors may be required as
storage tank sensors.
Only the standard sensor VR 10 from the
Vaillant accesories programme should be used.
The heating control using Vaillant components
is matched to the sensor characteristic curve
of the VR 10.
Temp. in °C R in kOhm Temp. in °C R in kOhm
10 5,363 55 0,806
15 4,283 60 0,671
20 3,372 65 0,562
25 2,700 70 0,473
30 2,176 75 0,399
35 1,764 80 0,339
40 1,439 85 0,288
45 1,180 90 0,247
50 0,973
Table 5.2 Standard sensor VR 10, allocation temperature
measurement value
5.2 Assembling VR 61 mixer module
Fig. 5.1 Opening the casing
⇒ Release the screw on the top of the casing .
⇒ Tilt the casing cover forwards slightly and remove.
1
2
Fig. 5.2 Fitting the mixer module VR 61
Key
1 Mounting apertures
2 Cable brackets
5 Assembly